USE-2

Product Description: Single conductor, 90C Wet/Dry. Insulated with chemically cross-linked polyethylene insulation.

Applications:
Appropriate for use in general purpose wiring for lighting and power - residential, commercial, and industrial buildings. Suitable for applica- tions that require superior flame retardance.

Construction:

Conductors: 14AWG - 500MCM fully annealed stranded bare copper per ASTM B3. Class B Stranding per ASTM B 8.
Insulation: Chemically cross-linked polyethylene
Colors: Black, Brown, Orange, Yellow, Green, White, Red, Gray, Blue.

Industry Listings & Standards:

  • UL Listed as XLP USE-2 or RHH/RHW-2 per Standard 44 and 854
  • ICEA S-95-658/NEMA WC-70
  • Federal Specification A-A-59544
  • 90°C Wet/Dry -40°C Rated
  • Gasoline and Oil Resistant II
  • C(UL)US RW90 1000V Listed
  • Sunlight Resistant
  • Direct Burial
  • RoHS Compliant

Part Number
AWG
Strand
Insulation
Thickness
Nominal
OD
Approximate Net Weight lbs/1M'
Copper Weight per lbs/1M'
Ampacity 90 C Wet/Dry
Inch
314
14
7
45
.169
22
12.78
35
312
12
7
45
.188
30
20.20
40
310
10
7
45
.212
45
31.72
55
308
8
7
60
.272
73
51.05
80
306
6
7
60
.310
107
80.90
105
304
4
7
60
.358
161
128.90
140
303
3
7
60
.382
193
162.50
165
302
2
7
60
.419
244
204.90
190
301
1
19
80
.484
325
253.40
220
3010
1/0
19
80
.523
399
319.40
260
3020
2/0
19
80
.567
491
402.80
300
3030
3/0
19
80
.617
606
510.20
350
3040
4/0
19
80
.673
751
660.00
405
30250
250 MCM
37
95
.765
860
772.00
455
30300
300 MCM
37
95
.820
1021
925.00
505
30350
350 MCM
37
95
.871
1184
1082.00
570
30400
400 MCM
37
95
.918
1345
1236.00
615
30500
500 MCM
37
95
1.003
1663
1543.00
700

The information contained on this specification is intended to be used a guide in product selection and is believed to be reliable.
ADC has made every effort to ensure the data shown above is accurate at the time of publication.  This specification is subject to change anytime without notice.